EXCEL WEB CONTROL SYSTEM NETWORKING WHITE PAPER
EN2B0396GE51 R1214 - 4 -
BACnet Communication Settings
If Excel Web controllers shall communicate to
devices in other IP subnets, then the default
gateway address must be set correctly. This is done
in the Honeywell CARE engineering tool.
General
To start with, APDU (Application Program Data Unit) settings
should be left as set by default in the Honeywell CARE
engineering tool. Change these settings only if required and
only after consultation of the person responsible for the
BACnet system integration.
If some Excel Web controllers of one CARE project are
located on BACnet/IP and other devices are located on
BACnet/MSTP networks, then the Max APDU Length should
be set to 480 (CARE will automatically set Max APDU
Length).
Max APDU Length
Max Segments accepted
APDU Timeout
BACnet Routers
BACnet Routers may connect different BACnet Networks with
different media. When for example devices in a
BACnet/MSTP network communicate with Excel Web
controllers on a BACnet/IP network, then there may be
restrictions to the APDU length. In this case some Messages
may not work.
It is recommended to set Max APDU Length to the smallest
APDU length in the network.
Please also refer to chapter Network Integration checklist for
more details.
BACnet Network numbers must be unique on the whole
BACnet internetwork.
BACnet /IP communication - NAT
routers
BACnet cannot be used over NAT routers.
The main workaround here is to use VPN, refer to the
“Honeywell BACnet architecture best practices” for more
details on this solution.
Another workaround is to have a BBMD in the BACnet
network, which is reachable over the internet. A remote
workstation can register itself as a foreign device with this
BBMD.
Broadcasts
In a BACnet System the below listed broadcasts are
mandatory in order to allow BACnet Clients and Servers to
identify each other.
Typically these broadcasts are created upon start-up of a
BACnet device or whenever the BACnet MAC address or the
route to a device is unknown.
“Who-Is” and “I-am” (used for identification of
BACnet devices on the network)
“Who-Is-Router-To-Network” (used to identify
BACnet routers on the network)
In addition the Excel Web controller will create the following
broadcasts as proprietary BACnet telegrams:
User Synchronization, created upon change,
deletion or addition of users.
This will synchronize the user administration for
Browser Access in all Excel Web controllers in the
same (CARE) project on the network.
BACnet Calendar Synchronization, created upon
change, deletion or addition of BACnet calendars.
This will synchronize all BACnet calendars in all
Excel Web controllers in the same (CARE) project
on the network.
Number of active Alarms in a controller
The above synchronization messages are issued whenever a
change occurs and cyclically.
Alarm synchronization is used between all Excel Web
controllers on the BACnet internetwork.
BACnet Broadcast Management Decice
If a BACnet Network spreads over different IP Subnets, then
the use of BBMDs is required. Please refer to chapter
Network Integration checklist for more details.
Terminal Access
For Linux download and for troubleshooting Excel Web
allows for terminal access on a dedicated serial port (serial
port no. 1)
Modem Access
Excel Web does not support BACnet/PTP.
Excel Web allows for access via analogue modem, ISDN
adapters or GSM adapters via its dedicated serial
port no. 3. In order to do so a remote connection via serial
interface needs to be established on the client PC/Laptop.
The following usage scenarios are typical:
Modem access with Internet Browsers (dial-in)
Modem access with the Honeywell CARE
engineering tool (dial-in)
NOTE: Due to network security issues, it is NOT
recommended to have a modem directly connected to an
Excel Web controller which is sitting in the network. Use the
RAS access of the network instead.